Ampacity Table
Ampacities of Insulated Conductors
Ampacities Of Insulated Conductors | ||||||
Not more three condcutors in Raceway or Cable or Earth (Directly Buried) | ||||||
Size | Copper Conductors | Aluminum Conductors | ||||
60oC (140o F) | 75oC (167o F) | 90oC | 60oC (140o F) | 75oC (167o F) | 90oC (194oF) | |
Wire Size (AWG or Kcmil) | Types | Types | Types | Types | Types | Types |
TW,UF | RHW,THW THWN, XHHW, USE,ZW | TBS,SA,SIS, FEP,FEPB, RHH,THHN, THWN,XHHW | TW,UF | RHW,THHW, THW,THWN, XHHW,USE | TBS,SA,SIS THHN,THHW, THW-2, THWN-2,RHH, RHW-2,USE-2, XHH,XHHW, XHHW-2,ZW-2 | |
18 | - | - | 14 | - | - | - |
16 | - | - | 18 | - | - | - |
141 | 20 | 20 | 25 | - | - | - |
121 | 25 | 25 | 30 | 201 | 201 | 251 |
101 | 30 | 35 | 40 | 25 | 301 | 351 |
8 | 40 | 50 | 55 | 30 | 40 | 45 |
6 | 55 | 65 | 75 | 40 | 50 | 60 |
4 | 70 | 85 | 95 | 55 | 65 | 75 |
3 | 85 | 100 | 110 | 65 | 75 | 85 |
2 | 95 | 115 | 130 | 75 | 90 | 100 |
1 | 110 | 130 | 150 | 85 | 100 | 115 |
1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
250 | 215 | 255 | 290 | 170 | 205 | 230 |
300 | 240 | 285 | 320 | 190 | 230 | 255 |
350 | 260 | 310 | 350 | 210 | 250 | 280 |
400 | 280 | 335 | 380 | 225 | 270 | 305 |
500 | 320 | 380 | 430 | 260 | 310 | 350 |
600 | 355 | 420 | 475 | 285 | 340 | 385 |
700 | 385 | 460 | 520 | 310 | 375 | 420 |
750 | 400 | 475 | 535 | 320 | 385 | 435 |
800 | 410 | 490 | 555 | 330 | 395 | 450 |
900 | 435 | 520 | 585 | 355 | 425 | 480 |
1000 | 455 | 545 | 615 | 375 | 445 | 500 |
1250 | 495 | 590 | 665 | 405 | 485 | 545 |
1500 | 520 | 625 | 705 | 435 | 520 | 585 |
1750 | 545 | 650 | 735 | 455 | 545 | 615 |
2000 | 560 | 665 | 750 | 470 | 560 | 630 |
1The load current rating and the overcurrent protection for conductor types shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. |
Correction Factors for Ambient Temperature Over 30oC, 86oF | ||||||
Ambient Temperature | For Ambient Temperature Over 30o C, 86o F, multiply the ampacities shwon above by the appropriate factor show below: | |||||
21-25o C, 70-77o F | 1.08 | 1.05 | 1.04 | 1.08 | 1.05 | 1.04 |
26-30o C, 78-86o F | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
31-35o C, 87-95o F | .91 | .94 | .96 | .91 | .94 | .96 |
36-40o C, 96-104o F | .82 | .88 | .91 | .82 | .88 | .91 |
41-45o C, 105-113o F | .71 | .82 | .87 | .71 | .82 | .87 |
46-50o C, 114-122o F | .58 | .75 | .82 | .58 | .75 | .82 |
51-55o C, 105-113o F | .41 | .67 | .76 | .41 | .67 | .76 |
56-60o C, 132-140o F | - | .58 | .71 | - | .58 | .71 |
61-70o C, 141-158o F | - | .33 | .58 | - | .33 | .58 |
71-80o C, 159-176o F | - | - | .41 | - | - | .41 |
3-Wire residential sevices, allowable ampacities [From NEC Table 310-15(B)(6)] | ||
Copper AWG | Aluminum AWG | Service Ampacity |
4 | 2 | 100 |
3 | 1 | 110 |
2 | 1/0 | 125 |
1 | 2/0 | 150 |
1/0 | 3/0 | 175 |
2/0 | 4/0 | 200 |
3/0 | 250 kcmil | 225 |
4/0 | 300 kcmil | 250 |